Dear members, Here with I am sharing a Presentation on 'FIRE SAFETY'. Prepared as simple as eating banana. This may useful to give trainings to your employees. Regards Srrinivasa Rao. M (Kundu B)
From India, Calcutta
From India, Calcutta
Dear Kundu,
Nice work. However, some small changes are needed for personnel downloading this presentation. The pump capacity and Jockey pump capacity do not need to be the same. We have main pumps with a capacity of 1000 m3/hr and Jockey pumps with a capacity of 350 m3/hr.
Additionally, the pressure of 7kg/cm should be at the remotest end. The water reservoir's size is not dependent on the pumps but is calculated based on the water requirement for fighting two major fires for 6 hours.
Therefore, I recommend that this presentation requires minor technical modifications. Let us be prepared for any questions regarding the technical details.
Best Regards
From India, Mumbai
Nice work. However, some small changes are needed for personnel downloading this presentation. The pump capacity and Jockey pump capacity do not need to be the same. We have main pumps with a capacity of 1000 m3/hr and Jockey pumps with a capacity of 350 m3/hr.
Additionally, the pressure of 7kg/cm should be at the remotest end. The water reservoir's size is not dependent on the pumps but is calculated based on the water requirement for fighting two major fires for 6 hours.
Therefore, I recommend that this presentation requires minor technical modifications. Let us be prepared for any questions regarding the technical details.
Best Regards
From India, Mumbai
Dear Mr. Kundu,
Thank you very much for the training PowerPoint. We are upgrading our EHS policy, and this presentation will definitely be helpful for our training purposes. If you have more such PowerPoint presentations on EHS for the pharma industry, please do share them with us.
Thanks once again,
Vidya More
Head of Quality, Ethypharm India
From India, Pune
Thank you very much for the training PowerPoint. We are upgrading our EHS policy, and this presentation will definitely be helpful for our training purposes. If you have more such PowerPoint presentations on EHS for the pharma industry, please do share them with us.
Thanks once again,
Vidya More
Head of Quality, Ethypharm India
From India, Pune
Dear Mr. Kundu,
Thank you very much for the training PowerPoint presentation. We are upgrading our EHS policy, and this presentation will definitely be helpful for our training purposes.
If you have more such PowerPoint presentations on EHS for the pharma industry, please do share them with us.
Thanks once again.
Vidya More
Head Quality, Ethypharm India
From India, Pune
Thank you very much for the training PowerPoint presentation. We are upgrading our EHS policy, and this presentation will definitely be helpful for our training purposes.
If you have more such PowerPoint presentations on EHS for the pharma industry, please do share them with us.
Thanks once again.
Vidya More
Head Quality, Ethypharm India
From India, Pune
Excellent presentation on Basic Fire Safety. Really, this is simple and useful for educating everyone, whether in a factory environment or at any other places such as offices, establishments, or malls. Keep sharing knowledge.
Best wishes,
S.B. Ramesh
TVSE, Dehradun
From India, Madras
Best wishes,
S.B. Ramesh
TVSE, Dehradun
From India, Madras
Dear Mr. Kundu,
Thank you for your PPT. It's quite helpful for us. If you wish, you can share anything related to the HR department, i.e., HR policies, compliances, labor welfare, and complete HR functions.
Regards,
V.P. Vijay Avinas
HR Manager
From India, Coimbatore
Thank you for your PPT. It's quite helpful for us. If you wish, you can share anything related to the HR department, i.e., HR policies, compliances, labor welfare, and complete HR functions.
Regards,
V.P. Vijay Avinas
HR Manager
From India, Coimbatore
Dear Neeraj,
Thank you for your response. The capacities provided are actuals in our industry. I am aware that these may vary from industry to industry. Once again, thanks for your suggestion.
Regards,
Srinivasa Rao. M
From India, Calcutta
Thank you for your response. The capacities provided are actuals in our industry. I am aware that these may vary from industry to industry. Once again, thanks for your suggestion.
Regards,
Srinivasa Rao. M
From India, Calcutta
Hi, Mr. Rao,
Very nice topic for a PowerPoint presentation. It is very useful in every organization for employees and also for family, society, our property, and human life, etc. If we are not aware of it, we can lose many things. So, awareness about fire safety is very important for each person to save lives and belongings.
Thank you and regards,
Minesh Kumari
From India, Delhi
Very nice topic for a PowerPoint presentation. It is very useful in every organization for employees and also for family, society, our property, and human life, etc. If we are not aware of it, we can lose many things. So, awareness about fire safety is very important for each person to save lives and belongings.
Thank you and regards,
Minesh Kumari
From India, Delhi
Dear Neeraj,
Nice one. But small changes are needed for personnel downloading this presentation. Pump capacity and Jockey pump capacity need not be the same. We have 1000 m3/hr main pumps and 350 m3/hr Jockey pumps.
Secondly, 7kg/cm should be at the remotest end.
Water reservoir does not depend on pumps but is calculated based on water requirement for fighting two major fires for 6 hours.
So I would suggest that this presentation needs minor modifications as far as technicality is concerned. Let us be prepared for - if someone asks WHY?
Best Regards
You have correctly brought out the relevant points as there cannot be a fixed template - it will vary with the variables of each site and requirement. Anyway, the details covered by the PPT are adequate and can be modified as per requirements. The comparison to "bananas" - not understood.
Regards,
Col J H Mayne
From India, Bangalore
Nice one. But small changes are needed for personnel downloading this presentation. Pump capacity and Jockey pump capacity need not be the same. We have 1000 m3/hr main pumps and 350 m3/hr Jockey pumps.
Secondly, 7kg/cm should be at the remotest end.
Water reservoir does not depend on pumps but is calculated based on water requirement for fighting two major fires for 6 hours.
So I would suggest that this presentation needs minor modifications as far as technicality is concerned. Let us be prepared for - if someone asks WHY?
Best Regards
You have correctly brought out the relevant points as there cannot be a fixed template - it will vary with the variables of each site and requirement. Anyway, the details covered by the PPT are adequate and can be modified as per requirements. The comparison to "bananas" - not understood.
Regards,
Col J H Mayne
From India, Bangalore
Hi to all seniors, my office size is 1800 sq. feet on the 1st floor, and the ground floor is 400 sq. feet. On the 1st floor, we have 10 computers and an administration office. Could you please advise on the type, quantity, and size of fire extinguishers that should be used in this space? I would appreciate a clear description.
Thank you.
From Kuwait
Thank you.
From Kuwait
Fire Extinguisher Requirements
As per IS 2190, you must provide one fire extinguisher for every 25 square feet. You may use CO2 multi-purpose extinguishers of 2, 3, and 4.5 kgs according to the above calculation.
For homes and labor camps, you can use the above types and water-type extinguishers.
Regards,
From India
As per IS 2190, you must provide one fire extinguisher for every 25 square feet. You may use CO2 multi-purpose extinguishers of 2, 3, and 4.5 kgs according to the above calculation.
For homes and labor camps, you can use the above types and water-type extinguishers.
Regards,
From India