Dear All,
I would like to add some more critical points in the safety of the LPG manifold (LOT):
  1. In case more than 1000 Kgs of LPG isntallation is there, then number of installtions should not be more than 4 (including stand by).
  2. Minimum of 3 meters distance from all sides shaould be avaialble in between the two installations.
  3. Vapourizer (other than Direct Heating) should be atleast 2 meters away from the LPG manifolds.
  4. Only Flameprrof (INtrinsically safe) electrical fittings should be insatlled.
Regards
Satnam Singh

From India
Wireless jamming device online wholesale 4g cell phone jammer Wholesales 4G Cell Phone Jammer - 4G Jammer - LoJack Jammer
From United States, Denver
can smbody tell me that what will be the safe distance between propane gas pipeline and electric cable supply
From India, undefined
LPG cylinders connected to Manifold does not required licence it is mentioned in Gas cylinder rules 2016.