Dear all,
I want more information about the fire extinguisher because one major incident happened in my near to company during the training & there may be the possibilty of the metal cap out of & dashed to the fatal person neck portion.(Extinguisher -DCP -5kg)
What may be the possibility of such incident.
As like ---
1.Not proper servicing
2.Metal cap loose
3.Anyone playing with extinguisher
4.Pressure built up inside due to chocking.
Any other reason pl.provide information to avoid further incident & what is the working pressure of the extinguisher.
Thanks & Reagrds,
L.P.Shinde
22nd January 2014 From India, Pune
Dear Mr. Shinde ,
before 2-3 years I heard same type of incident in one chemical industry . such incident can be avoided by taking due care as you mentioned.
One important point is Line of fire . One should not stand /put himself or herself in line of fire . while operating such equipment/instrument one must take position away from hazard's path . e.g when striking on fire extinguisher's knob , opening gas cylinder valve etc.
Good to see that you are participating in this forum and discussing your safety concerns.
Thanks
Abhay
22nd January 2014 From India, Thana
Dear all,
Abhay Sir -thank u
If anyone have IS 2171 & IS 2878 pl.provide the same to investigate above said incident.
As per investigation it seems that
1.may be due to metal cap kept lose by servicing agency during servicing / refilling
2.May be the manufacturing defect.
Pl.discuss & co operate
Thanks & Reagrds,
L.P.Shinde
22nd January 2014 From India, Pune
Dear Sir,
Following conditions will indicate as per IS 2190:19912 about probability of mechanical failure of an extinguisher and is unsafe for use:
1. Corrosion, wear or damage to threads of any pressure retaining part.
2. Corrosion of welds
3. Extensive general corrosion or severe pitting
Regards,
Hansa Vyas
23rd January 2014 From India, Udaipur
Dear Sir,

Sorry to hear about the incident.These type of incidents are not unheard of.

Seems like the incident occured on a stored pressure extinguisher with a CO2 cartridge.

The following can be the possible causes

Powder

There is also a chance of the discharge tube getting blocked due to caking in the powder (which can occur due to poor quality of powder, moisture getting in the powder, powder not taken out during periodic inspection and de-caked,

Powder not replaced on time.

Cap and throat

Loose threads on the cap or

Cap itself placed loose after periodic inspection,

Threads got disintegrated due to corrosion.

Vent hole on the cap was blocked and not cleared during servicing

The extinguisher might have been repeatedly used for demonstration and cap not placed properly after in situ refilling.

Operation

Plunger got stuck and more effort was put to activate

Someone tried to open the cap after the extinguisher failed to discharge without giving time for the gas to escape through vent hole.

Placing face right on top of the extinguisher thereby coming in line of fire.

Thanks and Regards

Unnikrishnan Nellanat

Process Specialist-HSE

Tata Consultancy Services Ltd
24th January 2014 From India, Trivandrum
I know a person who sells fire cease out product for extinguishing fire. Its the best product i know of.. you can Call her on 9833675915-Shivani
24th January 2014 From India, Mumbai
Dear Mr. unnikrishnan nellanat, Good inputs from your post . Thanks Hansa . In my views such emergencies need to include in Onsite emergency Plan . Thanks Abhay
24th January 2014 From India, Thana
Dear Abhay,
To avoid such incidents regular inspection of fire extinguishers need to be carried out and during fire training & demo it should be taught to trainees to keep their body away from fire extinguisher and this incident should be quoted as example so that they should know consequence of operating fire extinguisher in its line of fire and show them how to operate it while keeping our body away.This is what i use to do during my fire training sessions.
Regards,
Hansa
24th January 2014 From India, Udaipur
Dear Abhay,
To avoid such types of incident , regular inspection of fire extinguisher is to be carried out. Fire extinguisher kept outside area should be protected from outside environment( Heat, rain etc). Inplant training to be practiced regularly , yes its true such type of incidents do occur in pressurized CO2 cartridge type of extinguisher.
Regards
Deepak Dorik
26th January 2014 From India, Kalyan
Dear Sir,
Two more Incident was happened in the same manner, while operating the Fire Extinguisher the metal cap was removed and the Cylinder hitted the Operting Person he lost his live. Considering of above incident the Government has changed some rules in Fire Extinguisher. Instead of Bang Type Cylinder now the Squeeze type cylinder was introduced by the companies. Its very safe to use and also once DCP Cylinder is operated means powder will come totally. But in the Squeeze type Cylinder depending upon our requirement we can squeeze. Try to Use Squeeze type cylinder to avoid such type of incident in future.
29th January 2014 From India, Sriperumbudur
Reply (Add What You Know) Start New Discussion

Cite.Co - is a repository of information created by your industry peers and experienced seniors. Register Here and help by adding your inputs to this topic/query page.
Prime Sponsor: TALENTEDGE - Certification Courses for career growth from top institutes like IIM / XLRI direct to device (online digital learning)





About Us Advertise Contact Us
Privacy Policy Disclaimer Terms Of Service



All rights reserved @ 2017 Cite.Co™