Please explain what is the water pressure of fire hydrant and how the pressure is maintained while using?
Dear Hseofficer, yes as rightly said by manish,it is seven kg that we maintain in hydrant line. It is maintained by jockey pumps & desile pumps both by manual & auto mode. Regards, Hansa Vyas
Dear Hseofficer,
As explained by Manish & Hansa Vyas, the pressure in the Fire Hydrant system has to be 7 kg/cm2.
This pressure is to be maintained continusouly by providing Jockey pump.
To maintain the pressure while using (use in case of a fire) the hydrant system, it has to be operated on main electric pump. You should have Diesel operated pump as a stand by arrangement to use in case of power failure.
This whole system has to be maintained in 'Auto' mode. However, 'Manual mode' is also to be provided for testing & maintainance of the system.
Regards,
Shashikant.

Dear All
Very nice to see quick reply's and helping mentality of our forum members... Really nowadays with the involvement of more new members our forum is getting more active and helping one to many people for their day to day working...
Thanls to all and keep on sharing your expertise with us...

pl z tell me what is the legal provision of safety and also environment when you have to handle in factory involving Hazardous Processes
1.safety legal
2.Environmental legal
and dears tell me legal process before factory Installation and after Installation and process is being carried out
Regards
Shashikant Mane

Dear All,
Fire Hydrant System Pressure depends upon the Industry Category as per TAC recommendations. For Light Hazards /Ordinary Hazard if you have hydrant outlets > 100 than 7 kg/cm2 pressure is enough but if it is greater than 100 than it should be 7 to 8.8 kg/cm2.
But if your company is in High Hazrard category (A) and you have hydrant outlets between 20 -55 than pressure should be 7-8.8 kg/cm2 and if outlets are between 55-100 than it should be 7-10.5 kg/cm2.
Regards
Yadvinder Sharma

Dear Shashikant, hope this attachment may help you. Regards, Hansa Vyas

Attached Files
Membership is required for download. Create An Account First
File Type: xls statutoryfactorybeforeafter.xls (37.0 KB, 1488 views)

Dear Yadvinder, This data is related to the pump capacity that is required to maintain this pressure with the no. of outlets for different class of hazards. Regards, hansa Vyas
Dear Raghu, Please tell me about the quantity of Fire water to be stored at all times and how many hours it is enough to fight fire. regards, V.Gopalakrishnan
Dear Gopis,
Fire protection system continuously supply water until we close/reset the system. We stored enough liters of water in our fire tank as per NFPA standard/design. If water reaches the dead end in tank main pump will start automatically supply the water continuously, in some cases main pump shall failed, that time secondary pump its means jockey pump will start automatically supply the water continuously to FPS.