Dipil
Safety Consultant
Smbhappy
Finance, Hr, Sectarial Practices, Law And
Abhaygirish
Hr Executive
Vinoddigwal
Industry
+5 Others

Dear Seniors , As per factory act -1948 , kindly explain which 1. Tests : 2. Examinations : & 3.Inspections : in factory needed to be carried out by competent person. Regards,, ABHAY.
From India, Mumbai
Dear Abhay
Following are the few areas in which competent person needs to check and record to be kept.
1. Every hoist and lift shall be thoroughly examined by a competent person at least once in every period of six months.
2. All the lifting tools and tackels shall be thoroughly examined by a competent person at least once in every period of twelve months.
3. Every pressure vessel or plant in service shall be thoroughly examined by a competent person externally once in every period of six months
4. Stability certificate of all building in a factory to be obtained from competent person. This is valid for 5 years only.
There might be a lot more where competent person certification required... Hope to get more participation from other members...
Regards,
Dipil Kumar V

From India
The various Compliance under the Factories Act 1948 can be listed as under:

1. NOC from Local Fire Department
2. Water & Air Consent
3. DG Noise Pollution Certificate
4. Licence to Import & Store Petroleum
5. HSIDC Sewer Connection Approval
6. Calibration Certificate of Weighing M/c & Weights
7. Electricity Load Sanction Certificate
8. Certificate from Electorate Deptt., GGN.for Inspection of DG / Electrical Installation
9. Govt. Certificate for being an Authorised Competent Person for Inspecting & Issuing Fitness Certificate
10. Boilers Fitness Certificate from competent person
11. Compressor Fitness Certificate from competent person
12. Chains / Ropes Fitness Certificate from competent person
13. Lift running permission / Fitness Certificate from competent person
14. Certificate of Weighing M/c
15. Filter Inspections (installed on Drinking Water Cooler) report - Monthly
16. Drinking Water Test report for Micro Organism Analysis ( Every 6 months ) Water Sample must be collected by LAB.
17. ETP Inlet & Outlet Water Test (including Heavy Metals) Report

There may be more.

From India, Chandigarh
As per Factory Act 1948, Following are the few areas in which competent person to checked and Issued the Certificate and record to be kept.
1. Every hoist and lift shall be thoroughly examined by a competent person at least once in every period of Twelve months Certificate form No. 7A
2. All the lifting tools and tackels shall be thoroughly examined by a competent person at least once in every period of twelve months. form No.7A
3. Every pressure vessel or plant in service shall be thoroughly examined by a competent person externally once in every period of six months ceritificate in form No. 8
4. Stability certificate of all building in a factory to be obtained from competent person. This is valid for 3 years only.
With regards,
Balamurugan.L
Puducherry (Cell No.9488829216)

From India, Madras
@Balamurugan.L
Thanks for participating in the thread and share your knowledge with us...
You have mentioned in point no:4 that Stability certificate is valid for only 3 years... Can you please let us know the source of this info please...
As per my understanding as per Kerala Factories Rules it's 5 years...
Looking forward to hear from you.
Regards,
Dipil Kumar V

From India
Dear All,
Thanx.
Request all seniors Kindly guide For which :
A) Test(s) : 1. --- & F.A Ref.: ---
2. --- & FA Ref : --- and so on.
B) Examination(s) : 1. --- & FA Ref.: ---
2. --- & FA Ref : --- and so on
C) Inspection(s) : 1. --- & FA Ref.: ---
2. --- & FA Ref : --- and so on
P.S. : F.A - Factory Act ; Ref - Reference
Pls guide : differencr between Test , Examination & Inspection.
Kind Regards,
Abhay

From India, Mumbai
Dear All,

The following examination need to be conduct under the requirement of Factories Act-1948

1. Hoist & Lift - Sec 28 - 6 Month Frequency
2. Lifting Machines, Chains, Ropes & Lifting Tackles - Sec 29 - 12 Month Frequency
(Exception: For wire rope slings is 6 month as per the IS-12735 and frequency reduce to all if using in heating areas)
3. Pressure Vessel - Sec 31 - Frequency 6 Month (Externally)
Frequency 12 Month (Internally), and Hydrostatic in 4 Year
4. Safety Belt - Rule 67 A of Haryana Factory Rule Under Sec 32 of Factories Act - Frequency 6 Month
5. Building Stability - as discussed above
6.Dangerous Machines - Sec 21 (2)
Schedule V (Haryana Factories Rule) - Centrifugal Machines - No frequency depending upon Factory Inspector
Schedule VI - Power Press - 12 Month
7. Oven & Drier -Sec 41 & 112 Rule 66E- 6 Month
8. Ventilation System
9. Schedule VIII - Shot Blasting Machine - Weekly
10. Safety Devices -Part II - Appendix A
11. and... last is
Testing, examination and repair of plant & equipment- (1) All parts of plant, equipment and machinery used in the process which in the likely event of their failure may give rise to an emergent situation shall be tested by a competent person before commencing process and retested at an interval of two years after carrying out repairs to it. The competent person shall identify the parts of the plant, equipment and machinery required to be tested as aforesaid and evolve a suitable testing procedure. In carrying out the test as mentioned above in respect of pressure vessels or reaction vessels (Part II, Appendix A of Haryana Factories Rule)

I hope you get your answer correctly.

Thanks

Vinod Digwal
Competent Person (Haryana)

From India, Gurgaon
is there any Certificates required for CNC/VMC/HMC, Lathe machine, Welding machine, Cranes, Plasma cutting machine.......... Pls guide me
From India, Pune
Sir Can anyone tell me that who is responsible for testing the tools & tackles (Safety Officer or the Mechanical Department who are using it) Plz help me out its urgent
From India, New Delhi
Dear Sir, kindly guide is electric oven is required to be tested by competent person apart from above Regards: Jagbir Dhull